Revolution SLCX

ATEX Long Cased Axial Flow Fan
ATEX Construction Code: Ex h IIB+H2 T4 Gb

  • 7 standard sizes from 315mm to 710mm
  • Air volume flow rates up to 6.8 m3/s
  • Static pressure up to 872 Pa
  • Suitable for operating temperatures up to +40°C
  • Suitable for extract or supply systems
  • Available in AC

Quantity

Got a question about this product?

Email us or call us on +44 (0) 1384 275800

Overview

A range of ATEX rated duct mounted axial fans, manufactured in heavy gauge sheet steel. These units are designed to meet the requirements for Hazardous Areas with carbon filled anti-static impeller blades and protection to Ex h IIB+H2 T4 Gb.

Features and Benefits

Intelligent Design

Classified for constructional safety and the requirements stated in 2014/34/EU directive, Gas, Zone and ignition temperature protection to Ex h IIB+H2 T4 Gb.

Efficient Performance

Adjustable pitch aerofoil section impellers with blades made from high quality carbon filled anti-static material for enhanced performance. Hubs are die cast aluminium.

Warranty

Each SLCX has a 12 month warranty.

Specification

Casing

The all metal fan casing and guard provide a long lasting and robust construction. The units have been constructed from a single sheet of steel, with both motor and axial impeller mounted within the length of the unit casing. All casing parts are heavy gauge mild steelsheet, roll formed and welded, then hot dip galvanised to BS EN ISO 1461:2009 after fabrication.

Motors

Motors according to Gas Zone, Ignition Temperature and Protection to Ex h IIB+H2 T4 Gb.

Impellers

Adjustable pitch aerofoil impellers are provided with blades made from high quality carbon filled anti static material. Impellers are factory set at an angle to provide maximum performance. Hubs are manufactured from die cast aluminium alloy (LM24). Assembled impellers are dynamically balanced to ISO 14694 Grade G6.3.

Quality Management

Units are to be designed and manufactured with procedures as defined in BS EN ISO 9001. All Revolution SLCX units are to be tested to ISO 5801:1997 (airside performance) and BS 848 Part 2: 1985 (sound performance).

Customers Also Viewed

Compact SCD

Compact SCD

Short Cased Mounted Axial Flow Fan

Revolution SLC

Revolution SLC

Long Cased Axial Flow Fan

Raptor SFB
Limited Availability

Raptor SFB

ATEX Plate Mounted Axial Flow Fan

Select Available Next Day
Turboflow TF
Limited Availability

Turboflow TF

Contra Rotating Axial Flow Fan

Select Available Next Day